Refrigerant leakage: how to calculate F-gas emissions

Why small refrigerant leaks matter, how to estimate them from service records, and the CO2e factors for common refrigerants such as R410A, R404A, R32 and R134a.

By LCALens. Published 8 Oct 2026, 2 min read.

Part of Scope 1 emissions: fuels, vehicles and refrigerants.

Air conditioning, heat pumps, chillers and refrigeration all contain refrigerant, and all of them leak a little. Many refrigerants are fluorinated gases with global warming potentials in the thousands, so a few kilograms can be one of the largest items in a small company's Scope 1. The Corporate Standard counts these as fugitive emissions, from "intentional or unintentional releases". See Scope 1 emissions.

Estimating what leaked

You rarely measure a leak directly. The practical estimate is the mass of refrigerant added during servicing: if a technician tops a system up with 1.5 kg, about 1.5 kg escaped since the last service. Ask your maintenance contractor for a log per system with dates and kilograms added.

Other cases to include:

  • Equipment disposed of without recovering the refrigerant.
  • Accidental releases during repairs.
  • New installations where charging losses are recorded.

Factors for common refrigerants

DESNZ 2026 factors, kg CO2e per kg released ("total emissions including non-Kyoto products" column):

Refrigerantkg CO2e per kg
R404A3,943
R410A1,924
R407C1,624
HFC-134a (R134a)1,300
HFC-32 (R32)677
R290 (propane)0.06

The spread is enormous: a kilogram of R404A counts as almost 4 tonnes of CO2e, a kilogram of propane as 60 grams.

Worked example

A shop's service log for the year shows 2.0 kg of R404A added to the cold room and 1.2 kg of R410A added to the air conditioning:

  • 2.0 × 3,943 = 7,886 kg CO2e
  • 1.2 × 1,924 = 2,309 kg CO2e
  • Total: 10,195 kg CO2e, about 10 tonnes from 3.2 kg of gas.

Kyoto and non-Kyoto gases

DESNZ gives two columns for some refrigerants: emissions "including only Kyoto products" and "total emissions including non-Kyoto products". Older refrigerants such as R22 are controlled under the Montreal Protocol rather than the Kyoto Protocol. Corporate GHG inventories based on the GHG Protocol cover the Kyoto gases; if you also report non-Kyoto gases, show them separately and say so.

Reducing refrigerant emissions

The result depends on two things you can manage: how much leaks (maintenance, leak detection) and what the gas is (replacing high-GWP refrigerants when equipment is replaced). Recording kilograms per system each year shows which units leak most.

Calculate it

More on Scope 1: direct emissions

Sources

  1. GHG Protocol Corporate Accounting and Reporting Standard (revised edition), World Resources Institute / WBCSD (accessed 2026-10-08)
  2. UK Government GHG Conversion Factors for Company Reporting 2026, Department for Energy Security and Net Zero (accessed 2026-10-08)
  3. IPCC Global Warming Potential Values (August 2024), GHG Protocol (accessed 2026-10-08)

This guide explains methods and published data. It is not legal or assurance advice. LCALens is designed to align with the GHG Protocol and ISO 14064-1 but is not certified or endorsed by either body.